RV Copper Core General Purpose Single Core Soft Conductor Sheathless Cable

Implementation criteria: GB/T5023.3-2008
Rated voltage: U 0/U 450/750V
Rated temperature: 70 C
Advisory Service
  • Product Model, Production Range
  • Product Usage
  • Product Structure
  • Product Performance
  • Product Advantage (Selling Point)
  • Product Code Identification
  • Comprehensive Data of 60227 IEC 02 (RV) Wire
    Conductor nominal cross section (mm2) Conductor structure (NO. / mm) Insulation Thickness Required Value (mm) Upper limit of mean outer diameter (mm) Maximum conductor resistance (_/KM) at 20 C Minimum Insulation Resistance (M_/KM) at 70 Temperature
    lower limit Upper limit
    1.5 30/0.25 0.7 2.8 3.4 13.3 0.01
    2.5 50/0.25 0.8 3.4 4.1 7.98 0.009
    4 81/0.25 0.8 3.9 4.8 4.95 0.007
    6 84/0.30 0.8 4.4 5.3 3.3 0.006
    10 84/0.40 1 5.7 6.8 1.91 0.0056
    16 126/0.40 1 6.7 8.1 1.21 0.0046
    25 196/0.40 1.2 8.4 10.2 0.78 0.0044
    35 276/0.40 1.2 9.7 11.7 0.554 0.0038
    50 396/0.40 1.4 11.5 13.9 0.386 0.0037
    70 360/0.50 1.4 13.2 16 0.268 0.0032
    95 475/0.50 1.6 15.1 18.2 0.193 0.0032
    120 608/0.50 1.6 16.7 20.2 0.153 0.0029
    150 756/0.50 1.8 18.6 22.5 0.124 0.0029
    185 925/0.50 2 20.6 24.9 0.0991 0.0029
    240 1221/0.50 2.2 23.5 28.4 0.0754 0.0028
                 
    Comprehensive Data of 60227 IEC 06 (RV) 300/500V Wire
    Conductor nominal cross section (mm2) Conductor structure (NO. / mm) Insulation Thickness Required Value (mm) Upper limit of mean outer diameter (mm) Maximum conductor resistance (_/KM) at 20 C Minimum Insulation Resistance (M_/KM) at 70 Temperature
    lower limit Upper limit
    0.5 16/0.20 0.6 2.1 2.5 39 0.013
    0.75 24/0.20 0.6 2.2 2.7 26 0.011
    1 32/0.20 0.6 2.4 2.8 19.5 0.01
                 
    Comprehensive Data of 60227 IEC 08 (RV-90) 300/500V Wire
    Conductor nominal cross section (mm2) Conductor structure (NO. / mm) Insulation Thickness Required Value (mm) Upper limit of mean outer diameter (mm) Maximum conductor resistance (_/KM) at 20 C Minimum Insulation Resistance (M_/KM) at 70 Temperature
    lower limit Upper limit
    0.5 16/0.20 0.6 2.1 2.5 39 0.013
    0.75 24/0.20 0.6 2.2 2.7 26 0.012
    1 32/0.20 0.6 2.4 2.8 19.5 0.01
    1.5 30/0.25 0.7 2.8 3.4 13.3 0.009
    2.5 50/0.25 0.8 3.4 4.1 7.98 0.009

  • Copper-cored PVC insulated cables for power, lighting, household appliances, instruments and telecommunications equipment with rated AC voltage U 0/U of 450/750V or less

  • 1. The permissible working temperature of the cable for a long time shall not exceed 70 C.
    2. Cable laying temperature should not be lower than 0 C.
    3. When the allowable bending radius is less than or equal to 16mm, the cable outer diameter D should be no less than 4D, and no less than 6D when the cable outer diameter D is greater than or equal to 16mm.
    4. Insulation material is high-quality polyvinyl chloride, anti-aging, wear resistance, water-proof, oil-proof, chemical corrosion-proof, non-toxic and other characteristics.
    5. 100m/200m/3500m per volume or customized length