分享按钮

Hello! Welcome to the official website of Shenzhen Lilutong Technology Industrial Co., Ltd.!

BV Type Single Core Hard Conductor Sheathless Cable for General Purpose

Implementation criteria: GB/T5023.3-2008
Rated voltage: U 0/U 450/750V and below
Advisory Service
  • Product Model, Production Range
  • Product Usage
  • Product Structure
  • Product Performance
  • Product Advantage (Selling Point)
  • Product Code Identification



  • Comprehensive Data of 60227 IEC 01 (BV) Wire
    Conductor nominal cross section (mm2) Conductor structure (NO. / mm) Insulation Thickness Required Value (mm) Average Outer Diameter (mm) Maximum conductor resistance (_/KM) at 20 C Minimum Insulation Resistance (M_/KM) at 70 Temperature
    lower limit Upper limit
    1.5 1/1.38 0.7 2.6 3.2 12.1 0.011
    1.5 7/0.52 0.7 2.7 3.3 12.1 0.01
    2.5 1/1.78 0.8 3.2 3.9 7.41 0.01
    2.5 7/0.68 0.8 3.3 4 7.41 0.009
    4 1/2.25 0.8 3.6 4.4 4.61 0.0085
    4 7/0.85 0.8 3.8 4.6 4.61 0.0077
    6 1/2.76 0.8 4.1 5 3.08 0.007
    6 7/1.04 0.8 4.3 5.2 3.08 0.0065
    10 7/1.35 1 5.6 6.7 1.83 0.0065
    16 7/1.70 1 6.4 7.8 1.15 0.005
    25 7/2.14 1.2 8.1 9.7 0.727 0.005
    35 7/2.52 1.2 9 10.9 0.524 0.0043
    50 19/1.78 1.4 10.6 12.8 0.387 0.0045
    70 19/2.14 1.4 12.1 14.6 0.268 0.0035
    95 19/2.52 1.6 14.1 17.1 0.193 0.0035
    120 37/2.03 1.6 15.6 18.8 0.153 0.0032
    150 37/2.25 1.8 17.3 20.9 0.124 0.0032
    185 37/2.52 2 19.3 23.3 0.0991 0.0032
    240 61/2.25 2.2 22 26.6 0.0754 0.0032
    300 61/2.52 2.4 24.5 29.6 0.0601 0.003
    400 61/2.85 2.6 27.5 33.2 0.047 0.0028
                 
    60227 IEC 05(BV)300/500V Comprehensive Data of Type I Cable
    Conductor nominal cross section (mm2) Conductor structure (NO. / mm) Insulation Thickness Required Value (mm) Average Outer Diameter (mm) Maximum conductor resistance (_/KM) at 20 C Minimum Insulation Resistance at 90 Temperature(MΩ/KM)
    lower limit Upper limit
     0.5 1/0.80 0.6 1.9 2.3 36 0.015
     0.75 1/0.97 0.6 2.1 2.5 24.5 0.012
     1.0 1/1.13 0.6 2.2 2.7 18.1 0.011
                 
    60227 IEC 07(BV-90)300/500VComprehensive Data Rated Temperature of Type I Single Core Solid Conductor Cable: 90 C Insulation: PVC/E
    Conductor nominal cross section (mm2) Conductor structure (NO. / mm) Insulation Thickness Required Value (mm) Average Outer Diameter (mm) Maximum conductor resistance (_/KM) at 20 C Minimum Insulation Resistance at 90 Temperature(MΩ/KM)
    lower limit Upper limit
     0.5 1/0.80 0.6 1.9 2.3 36 0.015
     0.75 1/0.97 0.6 2.1 2.5 24.5 0.013
     1.0 1/1.13 0.6 2.2 2.7 18.1 0.012
     1.5 1/1.38 0.7 2.6 3.2 12.1 0.011
     2.5 1/1.78 0.8 3.2 3.9 7.41 0.009

  • Applicable to AC rated voltage U 0/U 450/750V and below power, lighting, household appliances, instruments. Copper Core PVC Insulated Cable for Instruments and Telecommunications Equipment

  • 1. The permissible working temperature of BV series cables should not exceed 70 C for a long time, and that of BV-90 series cables should not exceed 90 C (105 C) for a long time.
    2. Cable laying temperature should not be lower than 0 C.
    3. When the allowable bending radius is less than or equal to 16mm, the cable outer diameter (D) should be no less than 4D and no less than 6D when it is greater than 16mm.
    4. Insulation material is high quality PVC, which can be customized (anti-aging, wear resistance, low temperature resistance, oil resistance, chemical corrosion resistance, environmental protection, low smoke and halogen-free, etc.).
    5. 100m/200m/500m per volume or customized length
  • Editing...

  • Editing...

Copyright © 2018 Shenzhen Lilutong Technology Industrial Co., Ltd All rights reserved © Copying is prohibited without permission    ICP:粤ICP备11085524号
Technical Support: 南博网